I. Explosion-proof Structure and Sealing Failure
1. Damage to Flameproof Surfaces/Matching Surfaces
Symptoms: Scratches, corrosion, or deformation appear on the mating surfaces of the casing, leading to gap deviations.
Consequences: Internal explosion flames may leak out, causing an environmental explosion.
Solutions: Regularly inspect with feeler gauges and laser rangefinders; minor damage can be repaired by fine grinding; severe damage requires replacement of components.
2. Aging and Damage to Seals
Symptoms: Hardening and cracking of the sealing ring of the cable entry device; failure of the explosion-proof casing gasket.
Consequences: Dust, moisture, or flammable materials can intrude, reducing insulation performance.
Countermeasures: Strictly replace chemically resistant seals (such as nitrile rubber or fluororubber) according to the manual's replacement cycle.
II. Electrical Connections and Component Failures
1. Loose/Overheated Terminals
Symptoms: Sparks at the terminals, localized overheating of the casing, frequent tripping of the load equipment.
Causes: 1. Loose installation, vibration causing loosening, improper wire crimping (untinned multi-strand wires, excessive exposed length).
Solutions: Power off, tighten terminals; properly crimp wires (multi-strand wires need tinning or cold-pressed terminals, exposed length ≤3mm).
2. Component Overheating/Burning
Symptoms: Contactor and relay coil burnout, abnormally high surface temperature of resistors and frequency converters.
Solutions: Replace with explosion-proof components of the same specification; check load compatibility and ensure ventilation and heat dissipation.
3. Intrinsically Safe Circuit Failure
Symptoms: Intrinsically safe sensors have no signal, control box cannot collect data or drive the load.
Causes: Safety barrier failure (e.g., Zener diode breakdown, blown fuse), incorrect connection between intrinsically safe and non-intrinsically safe circuits, damaged wires causing grounding/short circuits.
Solutions: Disconnect non-intrinsically safe power supply, use a multimeter to measure the input/output voltage of the safety barrier; check the wiring diagram to confirm intrinsically safe circuit markings.
III. Environmental Adaptability Failures
1. Corrosion and Moisture
Symptoms: Rusting of equipment casing and internal components; decreased insulation performance.
Solutions: Select corrosion-resistant and moisture-proof explosion-proof electrical equipment (e.g., IP65 protection rating); place desiccant inside the equipment.
2. Abnormal Temperature
Symptoms: Ambient temperature too high or too low, exceeding the equipment's allowable operating range.
Solutions: Check equipment nameplate parameters to ensure operation within the allowable temperature range; add auxiliary heat dissipation measures in high-temperature environments.
3. Poor Ventilation and Heat Dissipation
Symptoms: Poor ventilation in equipment requiring ventilation; excessively high internal temperature.
Solutions: Regularly clean heat sinks and vents; check fan operation; replace fans if necessary.
IV. System and Management Failures
1. Improper Selection and Installation
Symptoms: The selected explosion-proof electrical equipment type is incompatible with the actual operating environment; improper installation location (e.g., areas susceptible to impact, vibration, or high temperatures). Countermeasures:
1. Strictly follow environmental zone classification (e.g., Zone 0, Zone 1, Zone 2) and equipment explosion-proof type selection; installation location should avoid areas susceptible to impact, vibration, or high temperatures.
2. Improper Maintenance
Manifestation: Inappropriate tools or methods were used during maintenance, compromising the equipment's explosion-proof performance.
Countermeasures: Explosion-proof tools must be used for maintenance; replacement parts must be original or certified models; unauthorized circuit modifications are strictly prohibited.
3. Lack of Inspection and Supervision
Manifestation: Equipment has been operating for a long time without regular inspections, and potential hazards have not been rectified in a timely manner.
Countermeasures: Establish a regular inspection system and entrust inspections to institutions with explosion-proof professional qualifications; ensure continuous supervision and promptly address any abnormal phenomena.
V. Other Common Faults
1. Control System Faults
Manifestation: Control circuit faults, such as relay or sensor malfunctions; the control system lacks necessary safety interlock devices.
Handling: Check the control circuit wiring, replace faulty relays or sensors; install necessary safety interlock devices.
2. Cable Laying Issues
Manifestations: Non-standard cable laying, causing interference with other pipes and equipment; lack of effective isolation measures when cables pass through different explosion-proof areas.
Solutions: Standardize cable laying to avoid cross-interference with other pipes and equipment; implement effective isolation measures at the boundaries of different explosion-proof areas.
3. Marking and Nameplate Issues
Manifestations: Unclear, missing, or incorrect explosion-proof markings; incomplete equipment nameplate information, making it impossible to accurately understand the equipment's explosion-proof parameters and performance.
Solutions: Regularly check explosion-proof markings and nameplate information to ensure clarity and completeness; re-mark as necessary.
Troubleshooting Principles
1. Safety First: Before handling any fault, the power supply must be disconnected to ensure environmental safety.
2. Professional Operation: Repair and replacement of explosion-proof equipment must be performed by qualified personnel using explosion-proof tools and certified accessories.
3. System Verification: After troubleshooting, the entire intrinsically safe system must be re-verified to ensure that the explosion-proof performance meets standards.
Prevention Recommendations:
1. Establish Equipment Files: Record in detail the equipment's selection, installation, inspection, and maintenance history for easy tracking and management.
2. Enhance Personnel Training: Regularly provide explosion-proof professional knowledge training to operators and maintenance personnel to improve their professional understanding.
3. Adopt Intelligent Monitoring: Consider installing online monitoring systems for temperature, vibration, etc., to achieve condition monitoring and predictive maintenance, and provide early warnings of potential faults.