Tension Sensor Installation Guide
1. Mechanical Alignment
Use a laser alignment tool to ensure the sensor axis and drive shaft are coaxial within 0.1mm. Eccentric loads can cause strain gauge debonding or measurement errors.
The mounting surface roughness must meet Ra 3.2, with a contact area greater than 85%.
2. Flange Rigid Fixing
Use 12.9-grade high-strength bolts and tighten them in three diagonal steps (refer to the torque manual).
Avoid striking or impacting the sensor to prevent damage to internal components.
3. Coupling Compatibility
An elastic diaphragm coupling is recommended to prevent vibration transmission from rigid couplings.
Allow 0.5-1mm axial clearance to compensate for thermal expansion.
4. Cable Protection
Routinely route signal cables through metal bellows, maintaining a distance of at least 30cm from power cables. Apply IP67-rated sealant to the joints.
5. Environmental Protection
Avoid high-temperature, humid, or corrosive environments. Install a protective cover if necessary. Usage and Calibration Procedures
1. Zero Calibration
In the unloaded state, perform the "Tare" operation through the HMI interface. Temperature-compensated models require a 30-minute warm-up in a 25°C environment.
2. Load Test
Gradually load the sensor to full scale and monitor output linearity (deviation should be <±1%FS).
During sudden unloading, the signal fallback time should be <50ms.
3. Parameter Settings
Set parameters such as the measurement range and sampling frequency according to actual requirements to ensure they match the actual scenario.
4. Maintenance Tips
Regularly inspect the cables and connectors, and keep the sensor clean and dust-free (especially the contact surface with the detection roller).
Avoid contact with liquids such as water and oil to prevent signal interference or corrosion.